model | GMV- VQ224WM/C-X* | GMV- VQ280WM/C-X* | GMV- VQ335WM/C-X* | GMV- VQ400WM/C-X* | GMV- VQ450WM/C-X* | GMV- VQ504WM/C-X* | GMV- VQ560WM/C-X* | GMV- VQ615WM/C-X* | ||
Capacity | HP | 8 | 10 | 12 | 14 | 16 | 18 | 20 | 22 | |
Cooling Capacity | Nom. | Kw | 22.4 | 28 | 33.5 | 40 | 45 | 50.4 | 56 | 61.5 |
Heating Capacity | Nom. | Kw | 16.2 | 16.2 | 18.5 | 23.5 | 23.5 | 33 | 33 | 37 |
Max. | Kw | 25 | 31.5 | 37.5 | 45 | 50 | 56.5 | 63 | 69 | |
Seer | Channel | – | 7.40 | 6.58 | 6.29 | 6.62 | 6.34 | 6.24 | 6.15 | 5.95 |
Cassette | – | 7.07 | 5.95 | 6.98 | 6.50 | 6.11 | 5.57 | 5.38 | 5.19 | |
SCOP | Channel | – | 5.18 | 5.18 | 5.44 | 4.87 | 4.87 | 4.89 | 4.80 | 4.80 |
Cassette | – | 4.47 | 4.47 | 4.55 | 4.18 | 4.18 | 4.05 | 3.95 | 3.95 | |
Power source | V / Ph / Hz | 380-415V 3N~50/60Hz | ||||||||
Max. Current/Fuse Current | A | 23.0/25 | 23.5/25 | 24.1/25 | 32.5/40 | 33.5/40 | 47.0/50 | 48.0/50 | 49.0/50 | |
Max. Power Input | Kw | 12.87 | 13.15 | 13.5 | 18.18 | 18.74 | 26.3 | 26.85 | 27.41 | |
Number of Connectable Internal Units | unit | 13 | 16 | 19 | 23 | 26 | 29 | 33 | 36 | |
Coolant Fluid Amount | Kg | 8.0 | 8.5 | 9.6 | 11.1 | 11.6 | 12.8 | 12.8 | 13.3 | |
Sound Pressure Level (Cooling) | dB(A) | 60 | 61 | 63 | 63 | 63 | 63 | 63 | 64 | |
Volume (Cooling) | Channel | dB(A) | 81 | 83 | 88 | 89 | 88 | 87 | 93 | 93 |
Cassette | dB(A) | 81 | 86 | 88 | 87 | 89 | 87 | 88 | 94 | |
Connection Pipe | Liquid | Mm | Φ9.52 | Φ9.52 | Φ12.7 | Φ12.7 | Φ12.7 | Φ15.9 | Φ15.9 | Φ15.9 |
A. Pressure Pipe Diameter | Mm | Φ15.09 | Φ19.05 | Φ19.05 | Φ22.2 | Φ22.2 | Φ25.4 | Φ25.4 | Φ25.4 | |
D. Pressure Pipe Diameter | Mm | Φ19.05 | Φ22.2 | Φ25.4 | Φ25.4 | Φ28.6 | Φ28.6 | Φ28.6 | Φ28.6 | |
Dimensions(GxDxY) | Product | Mm | 930×775×1690 | 930×775×1690 | 930×775×1690 | 1340×775×1690 | 1340×775×1690 | 1340×775×1690 | 1340×775×1690 | 1340×775×1690 |
Box | Mm | 1000×830×1855 | 1000×830×1855 | 1000×830×1855 | 1400×830×1855 | 1400×830×1855 | 1400×830×1855 | 1400×830×1855 | 1400×830×1855 | |
Net Weight/Gross Weight | Kg | 240/250 | 243/253 | 256/266 | 320/335 | 325/340 | 385/400 | 385/400 | 385/400 |
Multifunctional Study
GREE GMV6 Heat Recovery outdoor units can produce heating and cooling at the same time, as well as hot water for use hot water and underfloor heating system. When cooling the internal units, the use of hot water is obtained at a very low cost.
More Application Areas
The GMV6 HR can connect up to 80 internal units with a combination of up to 4 outdoor units, especially suitable for hotels and business centers.